Final | 11/30/2015 | 11/30/2015 | 11/30/2015 | P | PASS |
Eric Story
|
|
|
I installed the fault current label. That should be it. If you need to get inside the cabinet give me 20-30 minutes heads up. Phone #: ###-#### Inspection requested via web by jody mitchell final ok
|
Permanent Service | 9/2/2015 | 9/3/2015 | 9/3/2015 | A | PASS |
Eric Story
|
|
|
Just wanting to energize this service and do a final inspection next week. Phone #: ###-#### Inspection requested via web by jody mitchell p/s u/g n ok
|
Final | 8/27/2015 | 8/28/2015 | 8/28/2015 | P | FAIL |
Eric Story
|
|
|
Phone #: ###-#### Inspection requested via web by jody mitchell 110.24 available fault current calc shall be field marked-210.64 electrical service areas shall have a 120v receptacle within 50' of electrical equipment-408.36 (d) backfed breakers shall be secured in place (main breaker missing mounting screw-grounding required
|
Electrical Rough-In | 8/18/2015 | 8/19/2015 | 8/19/2015 | A | PASS |
Eric Story
|
|
|
Would like to do a morning inspection if possible so we can backfill tomorrow afternoon. Thanks Phone #: ###-#### Inspection requested via web by jody mitchell underground ok cover
|