Permit Information
Permit NumberELE15-02613
StatusFinaled
Name ENTERPRISE ELECTRIC
Site Address 420 S ORCHARD ST
Project Name 
Customer Number10608
ePlanReviewNo
Description
Alteration: Repair light fixtures, demo electric in wall, tie in power to fire control panel.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final8/25/20158/25/20158/25/2015PPASS
DetailsRock A. Hudson
Inspection requested via web by Clint Tate Final ok
Final8/24/20158/25/20158/25/2015PPART
DetailsRex Boyles
Inspection requested via web by Clint Tate corrections made emergency exits and lights still being installed temporary. occupancy ok
Final8/19/20158/20/20158/20/2015AFAIL
DetailsRex Boyles
The GC has requested we have the inspection as early as possible so he can get his building inspector in there next. Thanks for anything you can do. Our electrician contact is Julian ###-#### or Alex ###-####. Thanks again. Phone #: ###-#### Inspection requested via web by Clint Tate 300.11-identify seismic on troffers. 760.41(A)- fire alarm dedicated circuit shall be secured in the on position with lockoff. 760.41(B)- fire alarm circuit disconnect shall have red identfication.