Final | 11/17/2015 | 11/17/2015 | 11/17/2015 | P | PASS |
Rock A. Hudson
|
|
|
Bob Thomas Phone #: ###-#### Inspection requested via web by Kerri Hamilton Final ok
|
Final | 11/11/2015 | 11/12/2015 | 11/12/2015 | A | FAIL |
Rock A. Hudson
|
|
|
Bob Thomas Phone #: ###-#### Inspection requested via web by Kerri Hamilton 110.7- Wiring integrity- 2 receptacle outlets not working. Post outlet and north hall. Several luminaires not working, some flash. 210.8(B)- Receptacle outlets located within 6' of sink shall have GFCI protection.
|
Electrical Rough-In | 11/6/2015 | 11/9/2015 | 11/9/2015 | A | PASS |
Rock A. Hudson
|
|
|
Bob Thomas Phone #: ###-#### Inspection requested via web by Kerri Hamilton All grid rough in ok cover
|
Electrical Rough-In | 10/27/2015 | 10/28/2015 | 10/28/2015 | A | FAIL |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Kerri Hamilton 110.14- All unused openings shall be closed. 1/2" KO seals needed. 300.11- All luminaires shall be supported independant of grid. 300.15- MC cable shall terminate in a box. All near offices with open walls.
|
Electrical Rough-In | 10/23/2015 | 10/26/2015 | 10/26/2015 | A | PASS |
Daryl DeGrange
|
|
|
Bob Thomas Phone #: ###-#### Inspection requested via web by Kerri Hamilton rough-in ok cover walls
|
Electrical Rough-In | 9/11/2015 | 9/14/2015 | 9/14/2015 | A | PASS |
Rock A. Hudson
|
|
|
Bob Thomas Phone #: ###-#### Inspection requested via web by Kerri Hamilton Grid rough in ok cover
|
Electrical Rough-In | 8/31/2015 | 8/31/2015 | 8/31/2015 | P | PASS |
Rock A. Hudson
|
|
|
Bob Thomas Phone #: ###-#### Inspection requested via web by Kerri Hamilton. Wall rough in ok cover
|