Final | 11/25/2015 | 11/30/2015 | 11/30/2015 | A | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### Inspection requested via web by William Salts corrections made, ok final
|
Final | 11/24/2015 | 11/25/2015 | 11/25/2015 | P | FAIL |
Bob Reichert
|
|
|
Phone #: ###-#### Inspection requested via web by William Salts called, left correction notice, NEC 352.30 shall secure pvc within 3' of box, 210.52 shall add receptacle in upstairs room, BCC garage receptacles shall operate, shall provide box for hood, shall pepair sheetrok in backsplash
|
Permanent Service | 9/14/2015 | 9/15/2015 | 9/15/2015 | A | PASS |
Bob Reichert
|
|
|
Billy Phone #: ###-#### p/s u/g n ok
|
Electrical Rough-In | 9/14/2015 | 9/15/2015 | 9/15/2015 | A | PASS |
Bob Reichert
|
|
|
Billy Phone #: ###-#### corrections made, ri ok
|
Electrical Rough-In | 9/14/2015 | 9/14/2015 | 9/14/2015 | P | FAIL |
Bob Reichert
|
|
|
Phone #: ###-#### Inspection requested via web by William Salts met electrician, told to add ground crimps, 6" free conductor, nail plates, ground metal boxes, staple nm within 12' or 8", told to call for p/s, protect for attic access
|
Electrical Rough-In | 9/11/2015 | 9/14/2015 | 9/14/2015 | A | NR |
Rex Boyles
|
|
|
Phone #: ###-#### Inspection requested via web by William Salts 2 j man on job now, checked cards. Not ready for r/i
|
Electrical Rough-In | 9/9/2015 | 9/11/2015 | 9/11/2015 | P | FAIL |
Bob Reichert
|
|
|
Change time per Sara with Magic Valley Electric Phone #: ###-#### Inspection requested via web by William Salts called, 2 apprentices only working, took names, will have to recall, told to stop work without journeyman
|