Final | 11/16/2015 | 11/17/2015 | 11/17/2015 | A | PASS |
Daryl DeGrange
|
|
|
GFCI and receptacles have been replaced with tamper proof. Side door is open to get into shop. Phone #: ###-#### Inspection requested via web by Kurt Carlson correction done, final ok
|
Final | 11/12/2015 | 11/12/2015 | 11/12/2015 | A | FAIL |
Rock A. Hudson
|
|
|
All work is complete. Low voltage boxes, for speakers, are incomplete, owner to finish. Side door is open for access into shop. Phone #: ###-#### Inspection requested via web by Kurt Carlson 406.12(A)- All areas specified in 210.52, all 120volt 15 and 20 amp receptacle outlets shall be listed tamper resistant receptacles.
|
Electrical Rough-In | 10/6/2015 | 10/7/2015 | 10/7/2015 | A | PASS |
Rock A. Hudson
|
|
|
Walls and ceiling are ready for cover inspection. Interior panel is made up and turned on. Inspection requested via web by Kurt Carlson Garage rough in ok cover
|
Rough-In Permanent Service | 9/24/2015 | 9/24/2015 | 9/24/2015 | A | PASS |
Rock A. Hudson
|
|
|
New 400 amp service has been installed on southeast side of the new shop addition. New 200 amp sub panel is installed inside new shop. Feeds from IPCO and to existing house are installed into 400 amp service. 2 ground rods installed, existing house feed will be converted to 4 wire feed. Phone #: ###-#### Inspection requested via web by Kurt Carlson Service roughin only ok cover p/s u/g n ok
|