Final | 10/30/2015 | 11/2/2015 | 11/2/2015 | A | PASS |
Rock A. Hudson
|
|
|
final. please call duane for access @ ###-####. for questions on work please call jeff @ ###-#### Phone #: ###-#### Inspection requested via web by Andrea Creek Final ok
|
Final | 10/29/2015 | 10/30/2015 | 10/30/2015 | P | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Andrea Creek Garage only Final ok
|
Final | 10/28/2015 | 10/28/2015 | 10/28/2015 | P | FAIL |
Rex Boyles
|
|
|
Phone #: ###-#### Inspection requested via web by Andrea Creek 210.63- a 120 volt 15 or 20 amp receptacle shall be installed at an accessable location for the servicing of HVAC equipment. within 25 feet. 400.14-weathertite cord grip required for exterior connection.
|
Final | 10/21/2015 | 10/22/2015 | 10/22/2015 | A | FAIL |
Rock A. Hudson
|
|
|
please contact jeff @ ###-#### for questions about job Phone #: ###-#### Inspection requested via web by Andrea Creek 400.8- Flexible cords shall not run through holes in walls. 400.14- Flexible cord shall be protected by bushing or fitting where ran through holes in cover. Split system
|
Electrical Rough-In | 9/24/2015 | 9/25/2015 | 9/25/2015 | P | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Andrea Creek Addition to back of garage rough in ok cover
|