Final | 11/3/2015 | 11/4/2015 | 11/4/2015 | A | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Greg Traudt Final ok
|
Final | 10/6/2015 | 10/7/2015 | 10/7/2015 | A | CANC |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Greg Traudt Needed rough in permanent service inspection.
|
Rough-In Permanent Service | 10/7/2015 | 10/7/2015 | 10/7/2015 | P | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Greg Traudt Rough in ok cover p/s u/g n ok
|
Final | 10/5/2015 | 10/5/2015 | 10/5/2015 | P | CANC |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Greg Traudt Needed rough in permanent service.
|
Rough-In Permanent Service | 10/5/2015 | 10/5/2015 | 10/5/2015 | P | FAIL |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Greg Traudt 210.52- Shall have a receptacle outlet with in 12' of previous measured along floor line. M. bed. 300.4- NM cable shall be protected from physical damage where ran through bored hole that does not maintain 1 1/4" from framing surface. 320.23(A)- Cables ran with in 7' of attic access shall be protected by guard strips.
|