Final | 3/8/2016 | 3/8/2016 | 3/8/2016 | P | PASS |
Eric Story
|
|
|
Early afternoon, please - Rhonda Phone #: ###-#### corrections fixed final ok
|
Final | 3/4/2016 | 3/7/2016 | 3/7/2016 | A | FAIL |
Eric Story
|
|
|
would like call ahead; Rhonda Phone #: ###-#### 352.30 (a) PVC shall be supported with 36" of a cabinet 348.30 (a) FMC shall be supported 12" of a cabinet and not exceeding 4 1/2' 356.30 LFNC-B shall be supported with 12" of a box and not more the 6' 440.22 (c) protective device shall not exceed manufactures values (a/c)
|
Final | 10/23/2015 | 10/23/2015 | 10/23/2015 | P | PART |
Eric Story
|
|
|
verify a/c fuses correct size/in-use cover for weather proof/supporting for conduits partial ok
|
Final | 10/23/2015 | 10/23/2015 | 10/23/2015 | P | NR |
Eric Story
|
|
|
Rhonda Phone #: ###-#### not ready
|
Electrical Rough-In | 10/19/2015 | 10/19/2015 | 10/19/2015 | P | PASS |
Eric Story
|
|
|
Rhonda Phone #: ###-#### conduit feeding panel all wires ok conduit ok cover
|
Electrical Rough-In | 10/8/2015 | 10/9/2015 | 10/9/2015 | P | PART |
Eric Story
|
|
|
Mike Phone #: ###-#### foam sealing on exterior walls only need to verify panel installation for full cover
|
Conference | 10/5/2015 | 10/6/2015 | 10/6/2015 | A | DONE |
Eric Story
|
|
|
Rhonda Phone #: ###-#### conference on outlet placement and service to dog grooming areas and gfci protection
|