Final | 2/9/2016 | 2/10/2016 | 2/10/2016 | A | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### Inspection requested via web by David Nelson corrections made, ok final
|
Final | 2/8/2016 | 2/8/2016 | 2/8/2016 | P | FAIL |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by David Nelson 210.52(E)(1)- In a complete rewire a receptacle outlet shall be nstalled in front as well as in back of dwelling unit. 314.23(A)- Meter enclosure shall be rigidly secured to surface of dwelling. 352.30- Underground service riser and PVC conduit on back of garage shall be secured with in 3' of box, enclosure, or conduit body.
|
Final | 2/4/2016 | 2/5/2016 | 2/5/2016 | P | CANC |
Bob Reichert
|
|
|
Call ###-#### for access Phone #: ###-#### >> Inspection requested via web by David Nelson Inspection cancelled from web by: David Nelson
|
Final | 2/4/2016 | 2/5/2016 | 2/4/2016 | P | CANC |
Bob Reichert
|
|
|
Phone #: ###-#### >> Inspection requested via web by David Nelson Inspection cancelled from web by: David Nelson
|
Electrical Rough-In | 10/5/2015 | 10/6/2015 | 10/6/2015 | A | PASS |
Daryl DeGrange
|
|
|
Phone #: ###-#### Inspection requested via web by David Nelson Rough-in ok cover
|