Final | 10/15/2015 | 10/16/2015 | 10/16/2015 | A | PASS |
Rex Boyles
|
|
|
Call me if you need anything. Phone #: ###-#### Inspection requested via web by sam petterson corrections made final ok
|
Final | 10/12/2015 | 10/13/2015 | 10/13/2015 | A | FAIL |
Rex Boyles
|
|
|
Pam Carlson is the owner should you need access. Phone #: ###-#### Inspection requested via web by sam petterson wiring to heat pump ok wiring from heat pump to air handelers wired with TC-ER cable ran by TML. NEC 400.8(1)-flexable cords and cables shall not be used as a substitute for permenent wiring of a structure. OK if sleeved with raceway. This electrical work needs to be done by licensed electrical contractor.
|