Final | 12/22/2015 | 12/22/2015 | 12/22/2015 | A | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by daniel bibikov Final ok
|
Permanent Service | 11/4/2015 | 11/5/2015 | 11/5/2015 | A | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by daniel bibikov p/s u/g n ok
|
Permanent Service | 11/3/2015 | 11/4/2015 | 11/4/2015 | A | CANC |
Rock A. Hudson
|
|
|
Phone #: ###-#### >> Inspection requested via web by daniel bibikov Inspection cancelled from web by: daniel bibikov
|
Electrical Rough-In | 10/23/2015 | 10/23/2015 | 10/23/2015 | P | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by daniel bibikov Rough in ok cover
|
Electrical Rough-In | 10/22/2015 | 10/22/2015 | 10/22/2015 | P | FAIL |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by daniel bibikov 300.4- NM cable shall be protected from physical damage where ran through bored holes that do not maintain 1 1/4" from framing surface. 300.13- For multiwire branch circuits continuity of a grounded conductor shall not depend on device connections. 334.30- NM cable shall not be secured with in 1 1/4" from framing surface.
|