Final | 2/29/2016 | 2/29/2016 | 2/29/2016 | P | PASS |
Bob Reichert
|
|
|
Brandon Phone #: ###-#### corrections made, ok final
|
Final | 2/25/2016 | 2/26/2016 | 2/26/2016 | A | FAIL |
Daryl DeGrange
|
|
|
Phone #: ###-#### Inspection requested via web by Brandon Hillman 2012 energy code requires at least 50 % energy savings lamps throughout inside of structure. Washer receptacle within 6ft of a sink reqires GFCI protection. A/C conductors are #12 THHN on a 30 amp branch circuit. No service receptacle within 25 ft. of A/C unit. Island GFCI receptacle will not reset after test. Panel cover screws missing.
|
Rough-In Permanent Service | 11/23/2015 | 11/24/2015 | 11/24/2015 | A | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Brandon Hillman Rough in ok cover p/s u/g n ok
|
Rough-In Permanent Service | 11/23/2015 | 11/23/2015 | 11/23/2015 | P | FAIL |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Brandon Hillman 110.12- Check repair or replace damaged NM cable run to garage receptacles. 210.52(B)(1)- Dining area receptacle outlets shall be wired with 20 amp 120 volt small appliance circuit. 250.8- Main bonding screw shall be installed in panel for permenant service. 300.4- Speaker wire installed in family room where it may be damaged by drywall installation. 334.30- NM cable shall be secured with in 12" of master vanity light box.
|