Permit NumberELE15-03436
StatusFinaled
Name STARLITE ELECTRIC
Site Address 10733 W HOLLANDALE DR
Project Name 
Customer Number 
ePlanReviewNo
Description
Complete Installation (includes room count and per
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final2/29/20162/29/20162/29/2016PPASS
DetailsBob Reichert
Brandon Phone #: ###-#### corrections made, ok final
Final2/25/20162/26/20162/26/2016AFAIL
DetailsDaryl DeGrange
Phone #: ###-#### Inspection requested via web by Brandon Hillman 2012 energy code requires at least 50 % energy savings lamps throughout inside of structure. Washer receptacle within 6ft of a sink reqires GFCI protection. A/C conductors are #12 THHN on a 30 amp branch circuit. No service receptacle within 25 ft. of A/C unit. Island GFCI receptacle will not reset after test. Panel cover screws missing.
Rough-In Permanent Service11/23/201511/24/201511/24/2015APASS
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by Brandon Hillman Rough in ok cover p/s u/g n ok
Rough-In Permanent Service11/23/201511/23/201511/23/2015PFAIL
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by Brandon Hillman
110.12- Check repair or replace damaged NM cable run to garage receptacles.
210.52(B)(1)- Dining area receptacle outlets shall be wired with 20 amp 120 volt small appliance circuit.
250.8- Main bonding screw shall be installed in panel for permenant service.
300.4- Speaker wire installed in family room where it may be damaged by drywall installation.
334.30- NM cable shall be secured with in 12" of master vanity light box.