Final | 11/30/2015 | 12/7/2015 | 12/7/2015 | A | PASS |
Eric Story
|
|
|
Dedicated outlet/arch fault breaker in bedroom New bath outlet circuit/ 20 A breaker, #12 romex, gfci, outlet can lights in kitchen Thank you Phone #: ###-#### Inspection requested via web by Lonnie Sorichta final ok
|
Final | 11/4/2015 | 11/5/2015 | 11/5/2015 | P | FAIL |
Eric Story
|
|
|
If possible; late afternoon inspection. Thank you Phone #: ###-#### Inspection requested via web by Lonnie Sorichta 210.52 branch circuit added in bathroom shall be 20amp dedicated 210.12 branch circuit added in bedroom for computer shall be be AFCI protected
|