DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final3/28/20163/29/20163/29/2016APASS
DetailsBob Reichert
Key is hanging under lt sw inside garage door Phone #: ###-#### Inspection requested via web by Bryan Atkins ok final
Permanent Service11/11/201511/12/201511/12/2015APASS
DetailsDaryl DeGrange
Phone #: ###-#### Inspection requested via web by Bryan Atkins correction done,p/s u/g rec ok
Permanent Service11/4/201511/4/201511/4/2015PFAIL
DetailsRock A. Hudson
Please call Troy at the number listed before heading to site so he can meet you there for access. Phone #: ###-#### Inspection requested via web by Bryan Atkins
250.53(A)(2)- Where single water pipe bond exists it shall be supplemented by additional rod.
110.26- Work space shall be provided for electrical service. 30" wide and 36" deep.
Key hanging in garage on nail.
Tried to call contractor unable to leave message due to fax machine hooked to lline.
Permanent Service11/4/201511/4/201511/4/2015PCANC
DetailsBob Reichert
Please call Troy at the number above when headed to site for access. Phone #: ###-#### >> Inspection requested via web by Bryan Atkins Inspection cancelled from web by: Bryan Atkins