Final | 11/14/2016 | 11/15/2016 | 11/15/2016 | P | PASS |
Mark Moncarr
|
|
|
would like call ahead; emily Phone #: ###-#### corrections made. Final ok
|
Electrical Rough-In | 5/10/2016 | 5/11/2016 | 5/11/2016 | P | FAIL |
Eric Story
|
|
|
Emily-please call with an approx meet time Phone #: ###-#### 410.62(1) cord connected fixtures the receptacle needs to be within 6in within area of fixture 110.12 unused openings shall be closed BCO 4-05-32 No violation shall be retained Hot tub needs seperate permit an will not final out greenhouse until a permit and inspection have been retained. 350.12 LFMC & LFC shall not be used where subject to physical damage
|