Final | 3/11/2016 | 3/11/2016 | 3/11/2016 | P | PASS |
Eric Story
|
|
|
Phone #: ###-#### Inspection requested via web by kendall bender corrections fixed final ok
|
Final | 3/11/2016 | 3/11/2016 | 3/11/2016 | A | FAIL |
Eric Story
|
|
|
Phone #: ###-#### Inspection requested via web by kendall bender 210.8 receptacles in a garage shall have GFCI protection/receptacles within 6' of a ink shall have GFCI protection 406.5 receptacles shall be rigidly mounted 406.4 tamper resistant receptacles required 314.27 floor boxes shall be listed fr application faceplate for back w/p
|
Electrical Rough-In | 12/28/2015 | 12/29/2015 | 12/29/2015 | A | PASS |
Eric Story
|
|
|
Electrical floor heat Phone #: ###-#### Inspection requested via web by kendall bender master floor heat ok cover
|
Electrical Rough-In | 11/10/2015 | 11/12/2015 | 11/12/2015 | A | CANC |
Eric Story
|
|
|
Rick Phone #: ###-#### needed r/i p/s
|
Rough-In Permanent Service | 11/12/2015 | 11/12/2015 | 11/12/2015 | P | PASS |
Eric Story
|
|
|
Rick Phone #: ###-#### rough-in ok cover p/s u/g n ok
|