Final | 1/13/2016 | 1/14/2016 | 1/14/2016 | A | PASS |
Eric Story
|
|
|
Lock box is in mailbox the code is 7448 Phone #: ###-#### Inspection requested via web by Randy Fletcher corrections fixed final ok
|
Final | 1/11/2016 | 1/11/2016 | 1/11/2016 | P | FAIL |
Eric Story
|
|
|
Lock box is in mailbox and the code is 7448 Phone #: ###-#### Inspection requested via web by Randy Fletcher 210.52 (g)(1) branch circuit shall not supply any outlets outside of building 210.8(a)(5) in unfinished basements all 120v receptacles shall have GFCI protection Funds required to permit for final
|
Electrical Rough-In | 12/16/2015 | 12/17/2015 | 12/17/2015 | A | PASS |
Eric Story
|
|
|
Vacant home, Detached garage in back yard. Need ok to cover in the garage. Single Circuit feeding garage. Phone #: ###-#### Inspection requested via web by Randy Fletcher detached garage ok cover
|
Electrical Rough-In | 11/30/2015 | 11/30/2015 | 11/30/2015 | P | PASS |
Eric Story
|
|
|
Phone #: ###-#### Inspection requested via web by Randy Fletcher rough-in and underground to shop ok cover
|
Electrical Rough-In | 11/24/2015 | 11/25/2015 | 11/25/2015 | A | FAIL |
Eric Story
|
|
|
Building is unoccupied. Lock box code is 4995 Phone #: ###-#### Inspection requested via web by Randy Fletcher 210.11 (c)(1)(3) small apllaince branch circuits shall have 2 20 amp dedicated circuits in kitchen/ bathrooms shall have a dedicated 20amp circuit
|
Electrical Rough-In | 11/13/2015 | 11/13/2015 | 11/13/2015 | P | PASS |
Eric Story
|
|
|
Inspection for Idaho Power to restore power. Phone #: ###-#### Inspection requested via web by Randy Fletcher p/s o/h rec ok
|