Final | 3/23/2016 | 3/24/2016 | 3/24/2016 | A | PASS |
Rock A. Hudson
|
|
|
Curt Phone #: ###-#### Final ok
|
Final | 3/22/2016 | 3/23/2016 | 3/23/2016 | A | FAIL |
Rex Boyles
|
|
|
Curt Phone #: ###-#### 210.8(B)(5)- 120 volt receptacles within 6 foot of sinks shall have GFCI protection (kitchen). 210.12(A)-all 120 volt outlets (lights, sm.detectors and receptacles) in bdrms. shall have AFCI protection.
|
Electrical Rough-In | 12/3/2015 | 12/4/2015 | 12/4/2015 | A | PASS |
Rock A. Hudson
|
|
|
Working in basement, please call ahead - Curt Phone #: ###-#### Basement rec room with wet bar, down bed, bath, smokes to be inter connected at each floor level but not floor to floor. Rough in ok cover
|
Conference | 11/16/2015 | 11/16/2015 | 11/16/2015 | P | DONE |
Rock A. Hudson
|
|
|
Discussed minimum required receptacles, AFCI protection of bedrooms, dedicated bathroom receptacle circuit, and using SEU cable as subfeed to subpanel with a separate ground ran outside of cable for equipment ground.
|
Conference | 11/13/2015 | 11/16/2015 | 11/16/2015 | A | NH |
Rock A. Hudson
|
|
|
Curt Phone #: ###-#### No answer at door called and left message
|