Final | 1/4/2016 | 1/4/2016 | 1/4/2016 | P | PASS |
Rex Boyles
|
|
|
Tim Phone #: ###-#### corrections made final ok
|
Final | 12/30/2015 | 12/30/2015 | 12/30/2015 | P | FAIL |
Rex Boyles
|
|
|
Tim-please call 1 hr prior to meet for access Phone #: ###-#### Boise ordinance 4-05-32-no code violations shall be retained. 210.8 (B)(1)- all 120 volt receptacles in bathrooms in other than dwellings shall be GFCI protected. 210.8(B)(2) and (5) all 120 volt receptacles in kitchnens in other than dwellings shall have GFCI protection within 6 foot of sinks. 110.16- arc flash label on loadcenters required. Update panel schedule. Install receptacle covers on floor boxes.
|
Electrical Rough-In | 11/16/2015 | 11/16/2015 | 11/16/2015 | P | PASS |
Rex Boyles
|
|
|
Contact on site is Will Thomason Phone #: ###-#### Inspection requested via web by Todd Sellman r/i walls and ceilings ok
|