Final | 2/29/2016 | 2/29/2016 | 2/29/2016 | P | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by TOM BICANDI Final ok
|
Temporary Service | 11/24/2015 | 11/24/2015 | 11/24/2015 | P | FAIL |
Rock A. Hudson
|
|
|
590.6(B)- Temp power receptacles other than 120 volt shall have GFCI protection. 250 breaker did not trip when tested.
|
Rough-In Permanent Service | 11/23/2015 | 11/24/2015 | 11/24/2015 | A | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by TOM BICANDI Rough in ok cover p/s u/g n ok
|