Final | 11/25/2015 | 11/30/2015 | 11/30/2015 | P | PASS |
Bob Reichert
|
|
|
12 solar panels. AC micro-inverter system. No DC voltage. Enphase M250 Micro-Inverters, that are CSA, IEEE-1547, and UL-1741 listed. Ironridge Integrated Grounding System mid clamps, bonding straps and bonding lugs. And 280 watt SolarWorld panels, ETL listed.
A single home run, in metal conduit, is ran from the array to the knife switch, located next to meter base. From the knife switch to the breaker in the meter main. The solar breaker and knife switch are permanently marked for solar with weather proof labels, and the circuit numbers identified in the knife switch and on the panel schedule.
The inverters, panels and rails are all bonded with a number 6 ground that runs down to the service electrode that can be seen under the meter main.
The meter main where the solar breaker is located is exterior, so no inside access needed for this one.
Thanks guys, Ryan King Phone #: ###-#### Inspection requested via web by Ryan King ok final
|