Final | 3/18/2016 | 3/21/2016 | 3/21/2016 | A | PASS |
Rock A. Hudson
|
|
|
Corrections have been made. Thanks. Access is open or call Damion if trouble at ###-#### Phone #: ###-#### Inspection requested via web by Paula Gratiot Microwave not in recessed space above counter space. Contractor stated space is for storage. Final ok
|
Final | 3/17/2016 | 3/17/2016 | 3/17/2016 | P | FAIL |
Rock A. Hudson
|
|
|
Builder will have residence unlocked. Builder is Damion at ###-#### Phone #: ###-#### Inspection requested via web by Paula Gratiot 210.12- All 120 volt outlets located in bedrooms shall have AFCI protection. Smokes. 210.23- If microwave is in place installation will determine circuitry. Contactor stated space is for storage only. 1.2 KW micro on site. 210.52(C)(1)- A receptacle outlet shall be installed with in 24" of edge of counter top. 210.52(C)(3)- A receptacle outlet shall be installed at end of peninsula to serve counter space. 230.28- Service extends 5' above roof, secure guy kit that is installed. 314.23- AC disconnect shall be secured to surface of wall and cover secured.
|
Final | 11/30/2015 | 12/1/2015 | 12/1/2015 | A | CANC |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Paula Gratiot Needed rough in inspection
|
Electrical Rough-In | 12/1/2015 | 12/1/2015 | 12/1/2015 | P | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Paula Gratiot House unoccupied at this time. Full house rewire rough in ok cover
|