Final | 1/8/2016 | 1/8/2016 | 1/8/2016 | P | PASS |
Rock A. Hudson
|
|
|
Super indent will open it up he will be there in about 30 mins Phone #: ###-#### Inspection requested via web by Rowdy Monroe Final ok
|
Final | 1/7/2016 | 1/8/2016 | 1/8/2016 | A | FAIL |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Rowdy Monroe No access door code not working
|
Permanent Service | 12/4/2015 | 12/4/2015 | 12/4/2015 | A | PASS |
Rock A. Hudson
|
|
|
We rewired the service but the wire that was in the service was 2/0 copper. Phone #: ###-#### Inspection requested via web by Rowdy Monroe p/s u/g n ok
|
Electrical Rough-In | 12/2/2015 | 12/3/2015 | 12/3/2015 | P | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Rowdy Monroe Rough in ok cover
|
Permanent Service | 12/3/2015 | 12/3/2015 | 12/3/2015 | P | FAIL |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Rowdy Monroe 310.15(B)(7)- Minimum service entrance conductor size shall be 83% of service disconnect rating. 200x.83=166 amps. 2/0 copper or 4/0 alluminum minimum based on 75 degree terminations.
|