Final | 3/22/2016 | 3/22/2016 | 3/22/2016 | P | PASS |
Daryl DeGrange
|
|
|
Rod Phone #: ###-#### final ok
|
Electrical Rough-In | 12/7/2015 | 12/8/2015 | 12/8/2015 | A | PASS |
Daryl DeGrange
|
|
|
Rod Phone #: ###-#### correction done, ok covet
|
Electrical Rough-In | 12/7/2015 | 12/7/2015 | 12/7/2015 | P | FAIL |
Daryl DeGrange
|
|
|
Rod Phone #: ###-#### NEC 300.4 Nail Plates needed NEC 300.4 Cables and raceways paralled to framing member shall not be less than 1 1/4 from the nearest edge. NEC 362.12(9) ENT shall not be installed where subject to phyical damage. NEC 362.30 Securing and supporting with-in 3ft of an outlet box and at intervals exceeding 3ft.
|
Electrical Rough-In | 12/3/2015 | 12/3/2015 | 12/3/2015 | P | NR |
Daryl DeGrange
|
|
|
Rod Phone #: ###-#### Not ready at this time
|