Final | 2/29/2016 | 2/29/2016 | 2/29/2016 | A | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### Inspection requested via web by Darryn Coburn corrections made, ok final
|
Final | 2/18/2016 | 2/19/2016 | 2/19/2016 | A | FAIL |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Darryn Coburn 314.21- Drywall shall be repaired where boxes moved around windows so gap around box does not exceed 1/8". 314.25- Box in ceiling of back patio shall have a cover. 400.8(2)- Flexible cords shall not be run through walls. Power supply cord for LED drivers.
|
Rough-In Permanent Service | 12/11/2015 | 12/11/2015 | 12/11/2015 | P | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### Inspection requested via web by Darryn Coburn ri ok, p/s u/g n ok
|