Final | 1/20/2016 | 1/20/2016 | 1/20/2016 | P | PASS |
Rex Boyles
|
|
|
Warn Phone #: ###-#### corrections made final ok
|
Final | 1/19/2016 | 1/20/2016 | 1/20/2016 | A | FAIL |
Rex Boyles
|
|
|
Corrections under my care have been made. Phone #: ###-#### Inspection requested via web by Warren Fry 210.62 and 220.14(G)- showwindow receptacles required within 18" of top of window and 200 watts minimum per foot of window.
|
Final | 1/18/2016 | 1/19/2016 | 1/19/2016 | A | FAIL |
Rex Boyles
|
|
|
Phone #: ###-#### Inspection requested via web by Warren Fry 210.8 (B)(2)-all 120 volt 15 and 20 amp receptacles in other than dwellings shall have GFCI protection. No power to stock room receptacles also needing GFCI protection. No ground to hallway receptacle. UL listing for tortilla warmer
|
Electrical Rough-In | 1/11/2016 | 1/12/2016 | 1/12/2016 | A | PASS |
Rex Boyles
|
|
|
Need an inspection on ceiling and soffit wiring. Phone #: ###-#### Inspection requested via web by Warren Fry r/i hard lid and t bar ceilings ok
|
Electrical Rough-In | 12/7/2015 | 12/8/2015 | 12/8/2015 | A | PASS |
Rex Boyles
|
|
|
I need a wall rough-in inspection so they can sheetrock the walls. Any questions please give me a call. Call ###-#### for code to lock box if unit is not open. Phone #: ###-#### Inspection requested via web by Warren Fry r/i walls ok
|