Final | 2/23/2016 | 2/24/2016 | 2/24/2016 | A | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by David Nelson Final ok
|
Final | 2/23/2016 | 2/24/2016 | 2/23/2016 | A | CANC |
Rock A. Hudson
|
|
|
access 8800 Phone #: ###-#### >> Inspection requested via web by David Nelson Inspection cancelled from web by: David Nelson
|
Final | 2/22/2016 | 2/23/2016 | 2/23/2016 | A | FAIL |
Rock A. Hudson
|
|
|
Access code 0222 Phone #: ###-#### Inspection requested via web by David Nelson 110.12(B)- Receptacle outlets on kitchen counter not working and 1 in entry dead. 210.8-Unable to verify receptacle outlet on back deck east side at ceiling GFCI protection. Unable to check all outlets due to furniture in bedrooms moved in.
|
Rough-In Permanent Service | 12/9/2015 | 12/10/2015 | 12/10/2015 | A | PASS |
Rock A. Hudson
|
|
|
call ###-#### for access Phone #: ###-#### Inspection requested via web by David Nelson Rough in ok cover p/s o/h rec ok
|
Rough-In Permanent Service | 12/8/2015 | 12/8/2015 | 12/8/2015 | A | FAIL |
Rock A. Hudson
|
|
|
Please call for access code. Phone #: ###-#### Inspection requested via web by David Nelson 110.12(B)- 12-2 under panel damaged repair or replace. 210.12(A)- Outlets located in bedrooms shall have AFCI protection. 200.7(C)(1)- White conductors used for ungrounded conductors shall be identified other than white. 334.23- NM cable located with in 7' of attic access shall be protected be runners. Back bedroom area not damaged but homeruns replaced.
|
Permanent Service | 12/8/2015 | 12/8/2015 | 12/8/2015 | P | PASS |
Rock A. Hudson
|
|
|
Please call for access code. Phone #: ###-#### Inspection requested via web by David Nelson p/s o/h rec ok
|