Permit Information
Permit NumberELE15-03984
StatusFinaled
Name ENTERPRISE ELECTRIC
Site Address 11331 W CHINDEN BLVD
Project Name 
Customer Number 
ePlanReviewNo
Description
Alteration: electrical/lighting/fire alarm remodel
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final3/24/20163/28/20163/28/2016PPASS
DetailsRock A. Hudson
We are requesting a final inspection for this project on Monday 3/28/16 in the afternoon. Our contact is Rich @ ###-####. Thank you. Phone #: ###-#### Inspection requested via web by Clint Tate
Final ok
Final3/16/20163/16/20163/16/2016PCANC
DetailsRock A. Hudson
would like call ahead; Mike Phone #: ###-#### Contact information from ELE15-03985. Contractor at address on this permit did not request an inspection for today.
Electrical Rough-In1/29/20162/1/20162/1/2016PPASS
DetailsDaryl DeGrange
Request end of day inspection for temporary occupancy electrical final for B8 2nd floor. Phone #: ###-#### Inspection requested via web by Clint Tate Request for temporary occupancy ok
Final2/1/20162/1/20162/1/2016PPART
DetailsDaryl DeGrange
Request end of day inspection for temporary occupancy electrical final for B8 2nd floor. Phone #: ###-#### Inspection requested via web by Clint Tate Partial final- additional pendant lighting back ordered
Electrical Rough-In1/20/20161/21/20161/21/2016PPASS
DetailsRock A. Hudson
We are requesting a ceiling rough-in inspection for tomorrow 1/21/16 in the afternoon. Our contact is Rich @ ###-####. Thank you,
Phone #: ###-#### Inspection requested via web by Clint Tate Grid 2nd floor rough in ok cover
Conference1/21/20161/21/20161/21/2016PDONE
DetailsRock A. Hudson
Our contact is Rich @ ###-####. Thank you,
Phone #: ###-####
NEC 110.26(C)(2)-No clearance required on south side of new equipment due to no accessible panels on south side
Conference1/6/20161/6/20161/6/2016PDONE
DetailsRock A. Hudson
2nd meeting for addition of transfer switches and generators.
230.2(A)(4)- grouping not required for optional stand by systems,
110.26- panic hardware and door swings to be corrected.
All service entrance conductors will satisfy 230.6 with interior trans switch installed over underground service entrance and fused outdoor transfer switch.
Conference1/5/20161/6/20161/6/2016ADONE
DetailsRock A. Hudson
We are requesting a consult. Our contact is Rich @ ###-####. Thank you. Phone #: ###-#### Inspection requested via web by Clint Tate
Discussed the relocating of unfused service entrance conductors for the addition of generator and transfer switches. Talked about NEC 230.6 service entrance shall need to remain or need to be considered outside building until fused which shall be encased in minimum of 2" of concrete or run under 18" of earth or other recognized form.
Electrical Rough-In12/11/201512/11/201512/11/2015PPASS
DetailsRock A. Hudson
We are requesting a wall rough-in inspection for this afternoon. Our contact is Rich @ ###-####. Thank you,
Phone #: ###-#### Inspection requested via web by Clint Tate Walls located all over 2nd floor. 2nd floor wall rough in ok cover