Final | 12/17/2015 | 12/18/2015 | 12/18/2015 | A | PASS |
Rex Boyles
|
|
|
Inspection requested via web by David Green corrections made for p/s final ok
|
Permanent Service | 12/18/2015 | 12/18/2015 | 12/18/2015 | P | PASS |
Rex Boyles
|
|
|
Inspection requested via web by David Green p/s o/h rec ok
|
Final | 12/17/2015 | 12/17/2015 | 12/17/2015 | A | CANC |
Rex Boyles
|
|
|
Phone #: ###-#### Inspection requested via web by David Green needed p/s
|
Permanent Service | 12/17/2015 | 12/17/2015 | 12/17/2015 | P | FAIL |
Rex Boyles
|
|
|
Phone #: ###-#### Inspection requested via web by David Green As per manufacturers instructions on door, 70 amp maximum breaker except at lowest position. 250.53(a)(2)- additional ground rod required unless 25 ohms or less to earth
|