Final | 1/6/2016 | 1/7/2016 | 1/7/2016 | A | PASS |
Rock A. Hudson
|
|
|
Re-used existing wires from Panel "M" circuit #13 and fed a new 100 amp non-fused disconnect, from this disconnect we fed a new 480v to 240v 3 phase transformer, from the load side of the transformer we fed a new 3 phase 240v 200 amp fused disconnect, from this disconnect we fed the new Cyber Saw, we extended the existing conveyor motor lead from the Cyber Saw to the scrap conveyor. We also used existing conduit from Panel "A" to run a new dedicated 120v 20 amp circuit (#30) to the new computer cabinet for the Cyber Saw. Ask for James. If you have any questions please call Jeremiah at ###-####. Thank you! Phone #: ###-#### Inspection requested via web by Dan Mitchell Final ok
|
Electrical Rough-In | 1/6/2016 | 1/7/2016 | 1/7/2016 | A | PASS |
Rock A. Hudson
|
|
|
Re-used existing wires from Panel "M" circuit #13 and fed a new 100 amp non-fused disconnect, from this disconnect we fed a new 480v to 240v 3 phase transformer, from the load side of the transformer we fed a new 3 phase 240v 200 amp fused disconnect, from this disconnect we fed the new Cyber Saw, we extended the existing conveyor motor lead from the Cyber Saw to the scrap conveyor. We also used existing conduit from Panel "A" to run a new dedicated 120v 20 amp circuit (#30) to the new computer cabinet for the Cyber Saw. Ask for James. If you have any questions please call Jeremiah at ###-####. Thank you! Phone #: ###-#### Inspection requested via web by Dan Mitchell Rough in ok
|