Final | 1/21/2016 | 1/22/2016 | 1/22/2016 | A | PASS |
Rock A. Hudson
|
|
|
Bob Phone #: ###-#### Final ok
|
Final | 1/20/2016 | 1/21/2016 | 1/21/2016 | A | FAIL |
Rock A. Hudson
|
|
|
Bob Phone #: ###-#### 210.8- Receptacle outlet serving island counter space shall have GFCI protection. 406.12- All receptacle outlets installed in dwelling unit shall be tamper resistant type. Island receptacle.
|
Electrical Rough-In | 1/15/2016 | 1/19/2016 | 1/19/2016 | A | PASS |
Rock A. Hudson
|
|
|
Robert Phone #: ###-#### 3.7KW rated oven 15 amp draw, lock outs in place. Rough in ok cover
|
Conference | 1/8/2016 | 1/8/2016 | 1/8/2016 | P | DONE |
Rock A. Hudson
|
|
|
Owner called discussed the cooktop wiring . As per manufacurers instructions only 3 wire connection required due to a neutral not provide from factory. Cooktop frame will be bonded with an equpment grounding conductor.
|
Conference | 1/4/2016 | 1/4/2016 | 1/4/2016 | P | DONE |
Rock A. Hudson
|
|
|
Bob Phone #: ###-#### discussed the adding of circuits for new appliances. Separate grounds and neutrals for new oven and cook top, Securing under house, lockouts for hard wired appliances.
|