Permit NumberELE16-00042
StatusFinaled
Name RUMMER ELECTRIC
Site Address 6404 W POST ST
Project Name 
Customer Number34550
ePlanReviewNo
Description
Complete Installation (includes room count and per: new town house
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final4/24/20164/25/20164/25/2016PPASS
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by Neal Rumsey
Final ok
Final4/14/20164/15/20164/15/2016PFAIL
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by Neal Rumsey
210.8- Christmas GFCI device shall be located in a reakily accessible location. Below 6'7".
408,4- Circuit directory shall be completed at metermain on garage.
Rough-In Permanent Service1/12/20161/13/20161/13/2016PPASS
DetailsEric Story
Phone #: ###-#### Inspection requested via web by Neal Rumsey corrections fixed rough-i ok cover p/s o/h n ok
Rough-In Permanent Service1/12/20161/12/20161/12/2016PFAIL
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by Neal Rumsey
300.4- Furnace where NM cable passes through metal hole it shall be protcted from physical damage by bushing/connector.
300.4(G)- Raceway or connectors containing #4 or larger conductors shall have bushing installed to protect wiring.
314.17(C)- NM cable sheathing shall enter box minimum of 1/4". Ding room.
334.30- NM cable shall not be scured on edge.
250.134- Metal box in net panel shall be connnected to equipment grounding conductor.
Rough-In Permanent Service1/11/20161/11/20161/11/2016ANR
DetailsBob Reichert
Phone #: ###-#### Inspection requested via web by Neal Rumsey see comments for ELE16-00043, 2005 N Liberty