Final | 12/3/2018 | 12/4/2018 | 12/4/2018 | A | PASS |
Mark Moncarr
|
|
|
Re-scheduled from 12/3. Talked to homeowner. Ok final.
|
Final | 12/3/2018 | 12/3/2018 | 12/3/2018 | P | CANC |
Mark Moncarr
|
|
|
Bill Phone #: ###-#### Re-scheduled for 12/4
|
Final | 5/9/2018 | 5/11/2018 | 5/11/2018 | A | CANC |
Eric Story
|
|
|
Bill Phone #: ###-####-please call with an approx meet time
|
Final | 12/29/2016 | 12/30/2016 | 12/30/2016 | A | CANC |
Mark Moncarr
|
|
|
would like call ahead; Bill Phone #: ###-####. Canceled final and made it a roughin
|
Electrical Rough-In | 12/30/2016 | 12/30/2016 | 12/30/2016 | P | PASS |
Mark Moncarr
|
|
|
would like call ahead; Bill Phone #: ###-#### Move exterior light boxes down to avoid using pancake boxes due to box fill issues. Ok cover
|
Conference | 1/27/2016 | 2/5/2016 | 2/5/2016 | A | DONE |
Eric Story
|
|
|
###-####-Bill discussed service change, while on conference notice that the service was in violation of bco 4-05-31(C) and nec 230.3 service conductors shall not pass through an interior wall of a structure unless ecased in 2 " of concrete and shall not be greater then 4' in length.
|