Final | 3/25/2016 | 3/28/2016 | 3/28/2016 | A | PASS |
Rex Boyles
|
|
|
Kenny Phone #: ###-#### corrections made final ok permanent occupancy ok
|
Final | 3/23/2016 | 3/24/2016 | 3/24/2016 | A | FAIL |
Rex Boyles
|
|
|
Kenny Phone #: ###-#### 110.24-Available Fault current shall be posted at main disconnect. 210.63-a 120 volt receptacle outlet shall be installed within 25 foot of HVAC equipment.
|
Rough-In Permanent Service | 1/25/2016 | 1/26/2016 | 1/26/2016 | P | PASS |
Rex Boyles
|
|
|
Craig Phone #: ###-#### r/i ok p/s o/h n ok We will look for available fault current at final insp.
|