Information based on query as of Sunday, June 30, 2024.
Permit Information
Permit NumberELE16-00165
StatusFinaled
Name PERRINE ELECTRIC
Site Address 206 N 9TH ST
Project Name 
Customer Number 
ePlanReviewNo
Description
Alteration: Add bathroom, move lights and add outlets
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final3/1/20163/2/20163/2/2016APASS
DetailsRex Boyles
Call Scott 30 min before arrival ###-#### Phone #: ###-#### Inspection requested via web by danny perrine corrections made final ok
Final3/1/20163/1/20163/1/2016PCANC
DetailsRex Boyles
Call Scott 30 min before for access ###-#### Phone #: ###-#### >> Inspection requested via web by danny perrine Inspection cancelled from web by: danny perrine
Final2/25/20162/26/20162/26/2016AFAIL
DetailsRex Boyles
Call Scott 30 min prior ###-#### Phone #: ###-#### Inspection requested via web by danny perrine 110.16-electrical equipment such as panels that are in "other than dwellings" shall be marked "arc flash warning" to warn of potential arc flash. 210.8(B)(5)- GFCI protection required for receptacles within 6 foot of sinks such as (janitors closets)
Electrical Rough-In1/19/20161/19/20161/19/2016PPASS
DetailsRex Boyles
Phone #: ###-#### Inspection requested via web by danny perrine r/i ok bathroom walls and ceiling, serving counter