Final | 7/11/2016 | 7/11/2016 | 7/11/2016 | P | PASS |
Rock A. Hudson
|
|
|
Max Phone #: ###-#### Final ok
|
Electrical Rough-In | 6/20/2016 | 6/20/2016 | 6/20/2016 | P | PASS |
Rock A. Hudson
|
|
|
Max Phone #: ###-#### Discussed access to GFCI device for drinking fountain, opening at bottom of drinking fountain to be opened up for better access so not to be installed in hazardous location below. Grid rough in ok cover
|
Electrical Rough-In | 6/15/2016 | 6/16/2016 | 6/16/2016 | P | PASS |
Rock A. Hudson
|
|
|
Max Phone #: ###-#### Underground to and pole bases rough in ok cover
|
Permanent Service | 5/31/2016 | 6/1/2016 | 6/1/2016 | P | PASS |
Eric Story
|
|
|
Max Phone #: ###-#### p/s u/g n ok
|
Permanent Service | 5/25/2016 | 5/26/2016 | 5/26/2016 | P | NR |
Bob Reichert
|
|
|
Max Phone #: ###-#### told shall have stickers on gear for available fault current, grounding made up, labels for services
|
Electrical Rough-In | 5/13/2016 | 5/16/2016 | 5/16/2016 | A | PASS |
Rock A. Hudson
|
|
|
Max Phone #: ###-#### Underground to main service and to interior fire pumps rough in ok cover
|
Electrical Rough-In | 5/13/2016 | 5/13/2016 | 5/13/2016 | P | DONE |
Bob Reichert
|
|
|
Max Phone #: ###-#### still under construction
|
Electrical Rough-In | 4/29/2016 | 5/2/2016 | 5/2/2016 | P | PASS |
Rex Boyles
|
|
|
Max Phone #: ###-#### r/i ok 1st and 2nd floor walls and soffits
|
Electrical Rough-In | 4/26/2016 | 4/27/2016 | 4/27/2016 | A | PASS |
Rex Boyles
|
|
|
Max Phone #: ###-#### r/i exterior walls of hanger and office area including soffits ok
|
Conference | 3/17/2016 | 3/17/2016 | 3/17/2016 | P | DONE |
Rex Boyles
|
|
|
Max Phone #: ###-#### discuss hanger wiring methods. Max taking over project, asked him to ask Kevin P. to confirm hazardous location classification for this hanger. Fire pump conduits prevoisly installed ok . No breaks in conduits below 18inches. Follow article 513 in NEC.
|
Electrical Rough-In | 2/9/2016 | 2/10/2016 | 2/10/2016 | P | PASS |
Rex Boyles
|
|
|
Ben-underground Phone #: ###-#### r/i underslab in office areas ok to cover
|
Conference | 2/2/2016 | 2/3/2016 | 2/3/2016 | A | DONE |
Rex Boyles
|
|
|
Ben Phone #: ###-#### discuss hazardous location requirements for hangers. OK to run rigid metal conduit in areas of footings already poured to transition into office area (unclassified area). Meet article 513 in NEC everywhere else
|
Electrical Rough-In | 2/1/2016 | 2/1/2016 | 2/1/2016 | P | PASS |
Daryl DeGrange
|
|
|
Jake Phone #: ###-#### rough-in ok cover interior underground firepump service feeder conduits and UL listed floor boxes
|
Electrical Rough-In | 1/19/2016 | 1/20/2016 | 1/20/2016 | A | PASS |
Rex Boyles
|
|
|
Underground - Jake Phone #: ###-#### ufer ok
|