ELE-Aging Inspection | 8/2/2017 | 8/2/2017 | 8/3/2017 | P | CANC |
Eric Story
|
|
|
|
Final | 8/2/2017 | 8/2/2017 | 8/2/2017 | P | PASS |
Eric Story
|
|
|
Job was taken over by JES electric under permit #ele16-03596 ans has been finaled out. Will final this permit to close out permit number.
|
Conference | 1/20/2016 | 1/21/2016 | 1/21/2016 | A | DONE |
Rex Boyles
|
|
|
please contact Mike Dale for consultation. ###-#### thank you Phone #: ###-#### Inspection requested via web by Cyndi Dale Discuss what and where existing conduit and wiring and devices exposed after demo of old restaurant need replacing or ? OK to reuse existing conduit and wiring where compliant with 2014 NEC. Remove NM cable found in demoed walls and ceilings and exposed free conductors not in conduit. Replace boxes to small for new devices or GFCI receptacles.Re support conduits in kitchen, Fix broken 11/2" coupling for feeder. Install nailplates where necessary. New wiring shall be commercial type installation. Update where possible and accessable. Confirm good grounding electrode conductor for service and water bond. Satisfy 2014 NEC in all of building
|