Permit Information
Permit NumberELE16-00222
StatusFinaled
Name QUALITY ELECTRIC INC
Site Address 1401 S ROBERT ST
Project Name 
Customer Number16004
ePlanReviewNo
Description
New: Remodel second floor tenant space, including power, lighting, HVAC and fire alarm, per approved plans
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final6/7/20166/8/20166/8/2016APASS
DetailsRock A. Hudson
Andy Phone #: ###-#### Final ok
Final6/1/20166/2/20166/2/2016APART
DetailsRock A. Hudson
Andy Phone #: ###-####
2nd floor temp final ok
Electrical Rough-In4/12/20164/12/20164/12/2016PPASS
DetailsRex Boyles
Andy-Ceiling Phone #: ###-#### r/i tgrid ceilings 100% 2nd floor
Electrical Rough-In3/30/20164/1/20164/1/2016APASS
DetailsRock A. Hudson
Andy-ceiling Phone #: ###-####
Grid around sky lights, north offices rough in ok cover
Electrical Rough-In3/24/20163/24/20163/24/2016PPASS
DetailsRex Boyles
ceiling; Andy Phone #: ###-#### r/i ok 2nd floor t grid north half of large area. Also r/i ok 1st floor hard lid at back entry. Also asked Andy to relocate 2 raceways in 2nd flr server room in front of HVAC vav control box in ceiling to meet 110.26(A)(1) NEC
Conference3/21/20163/22/20163/22/2016ADONE
DetailsRex Boyles
Alan Phone #: ###-#### discuss change out of existing gear and installing new 120/208 volt 1200 amp main disconnect and distribution in basement. Need to get Fire Marshall ok for main disconnect location. Meet NEC 230.70(A)(1) and 230.6(1)or(2). Main disconnect shall be in a readily accessable location
Conference3/14/20163/15/20163/15/2016PCANC
DetailsRex Boyles
Andy Phone #: ###-#### needed r/i
Electrical Rough-In3/15/20163/15/20163/15/2016PPASS
DetailsRex Boyles
Andy Phone #: ###-#### r/i tgrid ceilings south half from soffit ok
Electrical Rough-In3/11/20163/11/20163/11/2016PPASS
DetailsBob Reichert
Andy Phone #: ###-#### east entry soffit ok cover
Electrical Rough-In2/24/20162/25/20162/25/2016APASS
DetailsEric Story
Andy Phone #: ###-#### entry receptacles and 4-gang and 2nd floor floor receptaces ok cover
Electrical Rough-In2/4/20162/4/20162/4/2016PPASS
DetailsBob Reichert
Andy Phone #: ###-#### walls only ok cover