Final | 7/26/2016 | 7/26/2016 | 7/26/2016 | P | PASS |
James Ady
|
|
|
Richard Phone #: ###-#### Corrections made final ok
|
Final | 6/24/2016 | 6/24/2016 | 6/24/2016 | P | FAIL |
James Ady
|
|
|
Rick Phone #: ###-#### 406.12 A Tamper resistant receps in dwelling units. Back Weather proof. 406.9 B 1. Receps outdoors shall be weather resistant. Front and Back Weather proof. 210.12 A Arc-fault protectiion requiered in bed rooms GFCI Breakers were installed not AFCI. 334.12 B 4. NM Cable shall not be exposed in damp locatiions. Front Patio Soffit. 3 non working receps in front room.
|
Electrical Rough-In | 2/18/2016 | 2/19/2016 | 2/19/2016 | A | CANC |
Rex Boyles
|
|
|
Vance Phone #: ###-#### needed r/i and p/s
|
Rough-In Permanent Service | 2/19/2016 | 2/19/2016 | 2/19/2016 | P | PASS |
Rex Boyles
|
|
|
Vance Phone #: ###-#### r/i ok p/s u/g n ok
|
Conference | 1/26/2016 | 1/28/2016 | 1/28/2016 | A | DONE |
Rex Boyles
|
|
|
Rick Phone #: ###-#### discuss code requirements for residential wiring, recept. placement, required circuits panel and sub feed tamper proof receps. etc.
|