Final | 2/10/2016 | 2/10/2016 | 2/10/2016 | P | PASS |
Rock A. Hudson
|
|
|
Call for access Phone #: ###-#### Inspection requested via web by John VanZandt Final ok
|
Permanent Service | 2/10/2016 | 2/10/2016 | 2/10/2016 | P | PASS |
Rock A. Hudson
|
|
|
Call for access Phone #: ###-#### Inspection requested via web by John VanZandt p/s u/g rec ok
|
Permanent Service | 1/27/2016 | 1/28/2016 | 1/28/2016 | A | FAIL |
Rock A. Hudson
|
|
|
call for access ###-#### Phone #: ###-#### Inspection requested via web by John VanZandt 250.24(A)- A premises wiring system supplied by a grounded AC service shall have a grounding electrode conductor connected to grounded conductor at service. 250.52(A)(1)- Underground metal water pipe if present shall be part of grounding electode system. 250.53(A)(2)- A single rod or pipe shall have supplemental electrode installed. 4-05-32- Code violations not to be retained. 334.30- SER cable installed under house in crawl shall be supported with supports not to exceed 4 1/2'.
|