Permit Information
Permit NumberELE16-00265
StatusFinaled
Name ENTERPRISE ELECTRIC
Site Address 400 S CAPITOL BLVD
Project Name 
Customer NumberC-16000
ePlanReviewNo
Description
Temporary Power Pole: Establish temporary power for crane and elevator.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Conference2/2/20162/9/20162/9/2016ADONE
DetailsRex Boyles
7:45 am morning conference on-site please contact is Tony ###-####. Thank you, Phone #: ###-#### Inspection requested via web by Clint Tate discuss fire pump wiring. Asked if Tony would run separate conduit from xformer straight to fire pump controller instead of in and out of main switchboard to satisfy 695.3(A)(1) for the ideal installation if possible. Single line method shown is ok if not possible due to number of conduits fitting in xformer window or sw. gear.
Final2/1/20162/2/20162/2/2016ACANC
DetailsRex Boyles
We are requesting a final inspection for temporary power for tomorrow Feb. 2, in the am. Our contact is Tony @ ###-####. Thank you Phone #: ###-#### Inspection requested via web by Clint Tate needed t/s
Temporary Service2/2/20162/2/20162/2/2016PPASS
DetailsRex Boyles
We are requesting a final inspection for temporary power for tomorrow Feb. 2, in the am. Our contact is Tony @ ###-####. Thank you Phone #: ###-#### Inspection requested via web by Clint Tate t/s u/g n ok Tony will post avaiable fault current asap
Electrical Rough-In1/28/20161/29/20161/29/2016PPASS
DetailsRex Boyles
Trench inspection for temp power. Phone #: ###-#### Inspection requested via web by Clint Tate r/i ok to cover t/s secondaries
Electrical Rough-In1/28/20161/28/20161/28/2016PCANC
DetailsRex Boyles
Trench inspection. Phone #: ###-#### >> Inspection requested via web by Clint Tate Inspection cancelled from web by: Clint Tate