Final | 3/9/2016 | 3/10/2016 | 3/10/2016 | A | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by kendall bender Receptacle outelt removed and blanked. Final ok
|
Final | 3/9/2016 | 3/9/2016 | 3/9/2016 | P | FAIL |
Rex Boyles
|
|
|
Phone #: ###-#### Inspection requested via web by kendall bender 210.8-all 120volt receptacles in other than dwellings shall have GFCI protection.(across from toilet)
|
Final | 3/8/2016 | 3/8/2016 | 3/8/2016 | P | FAIL |
Rex Boyles
|
|
|
Phone #: ###-#### Inspection requested via web by kendall bender 210.8(B)(1)-all 120 volt receptacles in "other than dwellings" shall have GFCI protection. 210.8-GFCI receptacle for drinking fountain not readily accessable. 110.16- All loadcenters, panels, etc. shall have arc flash hazard warning labels. Need 1/2 KO seal in gutter at back wall.
|
Electrical Rough-In | 2/4/2016 | 2/5/2016 | 2/5/2016 | A | PASS |
Rock A. Hudson
|
|
|
Wall rough in Phone #: ###-#### Inspection requested via web by kendall bender No exam areas all office and storage with lab room. Wall rough in ok cover
|