Final | 4/5/2017 | 4/10/2017 | 4/10/2017 | A | PASS |
Eric Story
|
|
|
James Phone #: ###-#### Final for main tie main ok
|
Electrical Rough-In | 11/16/2016 | 11/17/2016 | 11/17/2016 | P | PART |
James Ady
|
|
|
Main electrical room, please call ahead for access - James Phone #: ###-#### Recomended preformance testing as required by 230.95 (C) before energizing. Cable tray and terminations of 1st half of project ok
|
Conference | 9/7/2016 | 9/12/2016 | 9/12/2016 | A | DONE |
James Ady
|
|
|
Call half hour before to meet there // Mark Phone #: ###-#### Talked about allowing flex between EMT and Disconnect. Also discussed fabricating switch gear lid to allow DLO cable entrance
|