Final | 4/11/2016 | 4/11/2016 | 4/11/2016 | P | PASS |
Eric Story
|
|
|
ready for final and the door code is OCN if no one is there thanks Phone #: ###-#### Inspection requested via web by Brad Baker correction fixed final ok
|
Final | 4/7/2016 | 4/8/2016 | 4/8/2016 | A | FAIL |
Eric Story
|
|
|
Please call with any questions have a great day Phone #: ###-#### Inspection requested via web by Brad Baker 210.12 AFCI protection required for smokes and down bed 410.16 liminaires ina closet shall maintain 6" from storage space and shall be completely enclosed 422.31 permenetly installed appliances shall have means of lock-out(dishwasher) basements recepts in-op 110.7 Wiring integrity (basement storge/mech room needs to be completely re-done
|
Electrical Rough-In | 2/12/2016 | 2/16/2016 | 2/16/2016 | A | PASS |
Eric Story
|
|
|
The requested items have been repaired and ready for cover thanks Phone #: ###-#### Inspection requested via web by Brad Baker corrections fixed whole house remodel ok cover
|
Electrical Rough-In | 2/11/2016 | 2/11/2016 | 2/11/2016 | P | FAIL |
Eric Story
|
|
|
It should be open with people working, please call with any questions thanks Phone #: ###-#### Inspection requested via web by Brad Baker 300.4 nailplates needed@ type nm cable shall not be closer then 1 1/4" from face of faming member 334.30 type nm cabl shall be supported with 12" of a box 314 boxes shall be sized properly 590.6 all temporary recepts shall have GFCI protection remove wiring that is concealed in laundry room
|