Final | 10/25/2016 | 10/25/2016 | 10/25/2016 | P | PASS |
Mark Moncarr
|
|
|
Phone #: ###-#### Inspection requested via web by Spencer McLean Corrections made. Contractor put in GFI outlets where needed
|
Final | 10/4/2016 | 10/4/2016 | 10/4/2016 | A | FAIL |
Mark Moncarr
|
|
|
Phone #: ###-#### Inspection requested via web by Spencer McLean job listed as residential, outlets in garage need to be tamper resistant and GFI protected
|
Electrical Rough-In | 4/5/2016 | 4/5/2016 | 4/5/2016 | P | PASS |
Eric Story
|
|
|
Rough in inspection for cover Phone #: ###-#### Inspection requested via web by Spencer McLean corrections fixed rough-in ok cover
|
Electrical Rough-In | 4/4/2016 | 4/5/2016 | 4/5/2016 | A | FAIL |
Eric Story
|
|
|
Inspect for cover Phone #: ###-#### Inspection requested via web by Spencer McLean 511.3 all receptacles in a garage shall not be within 18" of garage floor 334.30 type NM cable shall be supported within 12" of a box or connector
|
Electrical Rough-In | 2/11/2016 | 2/12/2016 | 2/12/2016 | A | PASS |
Eric Story
|
|
|
Please inspect the underground feeder for the service to the building. Phone #: ###-#### Inspection requested via web by Spencer McLean underground from pole to shop ok cover
|