Final | 3/30/2016 | 3/30/2016 | 3/30/2016 | P | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by robert feller Final ok
|
Final | 3/28/2016 | 3/29/2016 | 3/29/2016 | P | FAIL |
Rock A. Hudson
|
|
|
Call if you need access lock box on front door. Phone #: ###-#### Inspection requested via web by robert feller 110.3- Items shall be wired as per manufacturers instructions. Receptacle in light grey room not working. Fans located in shower stalls shall have GFCI protection.. 330.30- MC and flex in millwork or cash wrap shall be secured within 12" of each box. 406.5(D)- Receptacles shall be flush or project from faceplate. Diamond plate areas. 422.30- A disconnecting means shall be provided for tanning bed. 110.25 lockout acceptable. Wiring compartment open. 422.52- Drinking fountain shall have GFCI protection. Unable to locate.
|
Electrical Rough-In | 2/19/2016 | 2/22/2016 | 2/22/2016 | A | PASS |
Rock A. Hudson
|
|
|
Call if you need access there is a lock box. We need new walls inspected for cover thanks. Phone #: ###-#### Inspection requested via web by robert feller Walls and hardlid rough in ok cover
|