Permit Information
Permit NumberELE16-00442
StatusFinaled
Name MOUNTAIN POWER ELECT
Site Address 1024 W BANNOCK ST
Project NameHyatt Place - Boise
Customer Number15-032
ePlanReviewNo
Description
New: Provide a complete electrical installation for a the new Hyatt Hotel.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final5/3/20175/3/20175/3/2017PPASS
DetailsMark Moncarr
Tom Phone #: ###-#### Ok final. Elevator lobby lights on floors 2-5 are temporary fixtures untill perm fixtures come in. Rooms 209, 409, 333, 433, and 533 also have temp fixtures in place while waiting on permanent fixtures.
Final5/2/20175/2/20175/2/2017PNR
DetailsMark Moncarr
Tom Phone #: ###-####
Final4/21/20174/21/20174/21/2017PPART
DetailsMark Moncarr
Jake Phone #: ###-#### TCO approved for construction/maintenance personnel only, no guests or hotel workers. A few locations lights are still needing to be installed, but locations are safed off.
Final4/19/20174/19/20174/19/2017PPART
DetailsMark Moncarr
Jake Phone #: ###-#### The rest of the 1st floor except kitch 1, kitch 2, lobby area and pool. Access to construction/maintenance personnel only. No hotel employees or guests.
Final4/18/20174/18/20174/18/2017PPART
DetailsMark Moncarr
Jake 1st floor Phone #: ###-#### 1st floor guest rooms and meeting rooms only. Maintanance personnel and construction personnel only. No hotel employees.
Final4/11/20174/11/20174/12/2017PPART
DetailsMark Moncarr
Jake Phone #: ###-#### Partial final. Access only to contruction and maintenance personnel. Rooms needing light install are 209, 309, 409, 509, 333, 433, and 533. Locations are safed off for now.
Final4/10/20174/10/20174/10/2017PPART
DetailsMark Moncarr
Jake Phone #: ###-#### Partial for contractors and maintenance personnel only, no hotel employees. Talked to Jake, there are a couple of lights still needing hung, but are safed off.
Final4/6/20174/7/20174/7/2017APART
DetailsMark Moncarr
Partial for 4th level, possibly 3 - Jake Phone #: ###-#### 4th floor rooms 401-442 partial. Maintenance and construction personnel only
Final4/5/20174/6/20174/6/2017APART
DetailsMark Moncarr
Jake Phone #: ###-#### Rooms 501-542 5th floor partial final. For maintenance and contruction personnel only, no housekeeping or hotel employees. Hotel is still considered construction site.
Permanent Service4/4/20174/4/20174/4/2017PFAIL
DetailsRock A. Hudson
ceiling grid; Jake Phone #: ###-####
Inspection for meyers cabinet on west side for sidewalk and street lighting must have seperate permit. Seperate service drop not part of building requires seperate permit.
Electrical Rough-In4/4/20174/4/20174/4/2017PPASS
DetailsRock A. Hudson
ceiling grid; Jake Phone #: ###-####
1st floor corridor east grid and 2nd floor corridor grid rough in ok cover
Electrical Rough-In4/3/20174/3/20174/3/2017PPASS
DetailsMark Moncarr
Jake Phone #: ###-#### 3rd floor corridor, and 4th/5th floor ceiling in house keeping roooms
Electrical Rough-In3/30/20173/30/20173/30/2017PPASS
DetailsMark Moncarr
Ceiling - Jake Phone #: ###-#### 4th floor grid in hallways ok cover
Electrical Rough-In3/23/20173/23/20173/23/2017PPASS
DetailsMark Moncarr
Tom or call Jake-ceiling Phone #: ###-#### Ok cover 1st floor laundry ceiling
Electrical Rough-In3/20/20173/21/20173/21/2017PPASS
DetailsMark Moncarr
Jake Phone #: ###-#### Cover for meeting rooms, cafe, and lobby
Electrical Rough-In3/9/20173/9/20173/9/2017PPASS
DetailsMark Moncarr
ceiling grid; Tom Phone #: ###-#### Ceiling ok cover for 1st floor vestibule, guest kitchen and fitness room
Electrical Rough-In3/7/20173/7/20173/7/2017PPASS
DetailsEric Story
ceiling grid; Jake Phone #: ###-####
Lobby area suspended ceilings and 5th floor corridor minus 3 areas were ames needed to be installed
Conference3/7/20173/7/20173/7/2017PDONE
DetailsEric Story
ceiling grid; Jake Phone #: ###-####
Discussed as per 406-12 stating all receptacles shall be tamper resistant type will need to replace all receptacles
Electrical Rough-In2/23/20172/23/20172/23/2017PPASS
DetailsMark Moncarr
Jake/ceiling cover for 1st floor Phone #: ###-#### Ok cover 1st floor ceiling in kitchen area, and 1st floor 2 managers offices.
Electrical Rough-In2/8/20172/8/20172/8/2017PPASS
DetailsMark Moncarr
Jake Phone #: ###-#### 2nd & 3rd floor elevator lobbies ok cover
Electrical Rough-In1/31/20171/31/20171/31/2017PPASS
DetailsMark Moncarr
Jake Phone #: ###-#### Lobby 1st floor west side, meeting rm 1 1st floor south side and 1st floor eastside rooms for dropped ceilings and conduit.
Electrical Rough-In1/27/20171/27/20171/27/2017PPASS
DetailsMark Moncarr
Jake Phone #: ###-#### Area 4 cans and 2 vestibule heaters with disc. 2 pool bathrooms
Electrical Rough-In1/26/20171/26/20171/26/2017PPASS
DetailsMark Moncarr
jake Phone #: ###-#### Ok cover. Mens and Womens bathroom 1st floor south side. 1st floor south side meeting room hard lid
Electrical Rough-In1/25/20171/25/20171/25/2017PPASS
DetailsMark Moncarr
jake Phone #: ###-#### ok cover. Area 3 soffits in bar and dining.
Electrical Rough-In1/23/20171/23/20171/23/2017PPASS
DetailsMark Moncarr
Jake Phone #: ###-#### Ground level Area 2 ceiling cover, and employee bathroom
Electrical Rough-In1/19/20171/19/20171/19/2017PPASS
DetailsMark Moncarr
jack Phone #: ###-#### 2nd floor corridor soffits ok cover
Electrical Rough-In1/17/20171/17/20171/17/2017PPASS
DetailsMark Moncarr
Jake Phone #: ###-#### 5th floor 8 cans in soffit in front of elevators Ok to cover
Electrical Rough-In1/13/20171/13/20171/13/2017PPASS
DetailsMark Moncarr
Jake Phone #: ###-#### 3rd floor corridor cans ok cover
Electrical Rough-In1/5/20171/5/20171/5/2017PPASS
DetailsMark Moncarr
Jake Phone #: ###-#### 4th floor corridor soffits ok cover
Electrical Rough-In12/29/201612/30/201612/30/2016APASS
DetailsMark Moncarr
Jake Phone #: ###-#### All 3rd floor room soffits. Ok cover
Electrical Rough-In12/22/201612/22/201612/22/2016PPASS
DetailsMark Moncarr
Jake Phone #: ###-#### Remainder of 1st floor lobby, and 1st floor sprinkler room S. side.
Electrical Rough-In12/20/201612/21/201612/21/2016PPASS
DetailsMark Moncarr
Jake Phone #: ###-#### 1st floor laundry walls. 3rd floor-all bath soffits. ok cover
Electrical Rough-In12/16/201612/16/201612/16/2016PPASS
DetailsMark Moncarr
ceiling, hallway soffits, 5th floor - Tom Phone #: ###-#### Hallway soffits 5th floor ok cover
Electrical Rough-In12/13/201612/14/201612/14/2016APASS
DetailsMark Moncarr
Jake Phone #: ###-#### ok cover Area 7,8 and 4 baths area 9- 1st floor
Electrical Rough-In12/9/201612/9/201612/9/2016PPASS
DetailsRock A. Hudson
Jake Phone #: ###-####
Discussed wiring being damaged by unlicensed laborers. Damage occurs with out electrical contractor being notified creating patches in firewalls and ceilings. Will try to catch individuals next week when working on 3rd floor. 1st floor corridors and offices noted on print and 4th floor drop ceilings rough in ok cover
Permanent Service12/9/201612/9/201612/9/2016PPASS
DetailsRock A. Hudson
Jake Phone #: ###-####
Contractor doing work over weekend. Will call for inspection Monday to check work. Placed service sticker in old disconnect. Changing from 100amp to 200amp. New 200amp disconnect will be on interior back to back.
p/s o/h rec ok
Electrical Rough-In12/5/201612/6/201612/6/2016APASS
DetailsMark Moncarr
Jake Phone #: ###-#### 2 light poles bases west side off 10th ok cover
Electrical Rough-In12/2/201612/2/201612/2/2016PPASS
DetailsMark Moncarr
Jake Phone #: ###-#### Area 2&3 ground floor west side
Electrical Rough-In12/1/201612/1/201612/1/2016PPASS
DetailsMark Moncarr
Pole base - Jake Phone #: ###-#### 4 light pole cages south side.
Electrical Rough-In11/22/201611/23/201611/23/2016PPASS
DetailsMark Moncarr
Jake Phone #: ###-#### ok cover AREA1 first fl.
Electrical Rough-In11/21/201611/21/201611/21/2016PPASS
DetailsMark Moncarr
Jake Phone #: ###-#### Lt pole on W side, and rest of 5th floor ceilings
Electrical Rough-In11/17/201611/17/201611/17/2016PPASS
DetailsMark Moncarr
Jake//ceiling soffits Phone #: ###-#### ok cover rm 501-521 except 519. 4th floor rm 409, 413, 415.
Electrical Rough-In10/13/201610/13/201610/13/2016PPASS
DetailsMark Moncarr
Jake Phone #: ###-#### ok cover 2nd floor rms
Electrical Rough-In9/30/20169/30/20169/30/2016PPASS
DetailsMark Moncarr
Jake would like the inspection as late as possible. Phone #: ###-#### West side of 4th floor outlets placement as per Daryl DeGrange rough ok cover. All of 3rd floor outlet placement as per Daryl DeGrange rough ok cover
Electrical Rough-In9/28/20169/28/20169/28/2016PPASS
DetailsRock A. Hudson
Jake would like AM if possible Phone #: ###-####
Level 4 unit 425 to east receptacle additions rough in ok cover
Electrical Rough-In9/22/20169/23/20169/23/2016PPASS
DetailsJames Ady
Jake Phone #: ###-#### n 5th floor added receps ok to cover
Electrical Rough-In9/21/20169/22/20169/22/2016APASS
DetailsMark Moncarr
Jake Phone #: ###-#### checked jumper from pool to hottub for 1 whole equipotential plane
Conference9/13/20169/14/20169/14/2016ADONE
DetailsJames Ady
Jake Phone #: ###-#### Discussed wall space layout for recepticles as well as bathroom recep requirements
Electrical Rough-In9/12/20169/12/20169/12/2016PFAIL
DetailsJames Ady
Jake Phone #: ###-#### 210.60 Guest rooms suites and similar occupantcies shall comply with 210.52 A and D.
210 52 A 1 receps shall be installed so that no space along floor is more than 6 feet fromm a receptacle
Permanent Service9/2/20169/2/20169/2/2016PPASS
DetailsMark Moncarr
Jake Phone #: ###-#### correction made.
Permanent Service9/1/20169/1/20169/1/2016PFAIL
DetailsJames Ady
Jake Phone #: ###-#### 110.24 A availabel fault current shall be feild marked
Electrical Rough-In8/26/20168/26/20168/26/2016PPASS
DetailsMark Moncarr
Tom Phone #: ###-#### S. wall cover for house keeping rooms levels 1-5 rough in ok
Electrical Rough-In8/17/20168/17/20168/17/2016PPASS
DetailsJames Ady
jake Phone #: ###-#### 5th floor ok to cover
Electrical Rough-In8/4/20168/5/20168/5/2016APASS
DetailsEric Story
Jake Phone #: ###-####
3rd and 4th corrridor walls and cieling only ok cover. Discussed with GC that all water lines and equipment within 6' above panels shall not be there and will remove what is in the dedicated area.
Electrical Rough-In7/27/20167/28/20167/28/2016APASS
DetailsEric Story
Jake Phone #: ###-####
first floor north electrical room(only one receptalce and data on north wall was all there was to look at )ok cover
Conference4/14/20164/14/20164/14/2016PDONE
DetailsEric Story
jake Phone #: ###-#### discussed repairing or completely replacing conduit that was hit. conduit was installed in 1930 therefor find a listed part maybe hard to come by. most likely will be refeeding all of what it was powering up.
Electrical Rough-In3/31/20163/31/20163/31/2016PPASS
DetailsEric Story
Jake underground only Phone #: ###-#### west end underground ok cover
Electrical Rough-In3/23/20163/24/20163/24/2016APASS
DetailsEric Story
underground; Jake Phone #: ###-#### underground for primary feeders ok cover
Electrical Rough-In3/15/20163/15/20163/15/2016PPASS
DetailsEric Story
Jake//underground Phone #: ###-#### east side first floor underground ok cover
Electrical Rough-In3/14/20163/14/20163/14/2016PCANC
DetailsEric Story
underground Phone #: ###-#### not ready at this time will call back for 3/15/16
Electrical Rough-In3/11/20163/11/20163/11/2016PNR
DetailsDaryl DeGrange
Jake Phone #: ###-#### Contractor called, wants to reschedule for monday 3/14/16