Final | 3/30/2016 | 3/31/2016 | 3/31/2016 | A | PASS |
Eric Story
|
|
|
Phone #: ###-#### Inspection requested via web by John VanZandt correction fixed final ok
|
Final | 3/29/2016 | 3/30/2016 | 3/30/2016 | A | FAIL |
Eric Story
|
|
|
Phone #: ###-#### Inspection requested via web by John VanZandt 406.5 receptacle mounting shall be rigidly fastened in place@switches as well 406.6 faceplates required
|
Electrical Rough-In | 3/9/2016 | 3/9/2016 | 3/9/2016 | P | PASS |
Eric Story
|
|
|
Ceiling Insp. Phone #: ###-#### Inspection requested via web by John VanZandt correction fixed cielings ok cover
|
Final | 3/8/2016 | 3/8/2016 | 3/8/2016 | P | FAIL |
Eric Story
|
|
|
Ceiling Insp, call for access Phone #: ###-#### Inspection requested via web by John VanZandt 110.12 unused openings required 314.17(a) openings shall be closed in a approved manner 314.25 covers required
|
Electrical Rough-In | 2/22/2016 | 2/23/2016 | 2/23/2016 | A | PASS |
Rex Boyles
|
|
|
inspection on 4 walls, call for access Phone #: ###-#### Inspection requested via web by John VanZandt r/i walls ok
|