Temporary Service | 2/25/2016 | 2/25/2016 | 2/25/2016 | P | PASS |
Bob Reichert
|
|
|
Reinspection on temp pole Phone #: ###-#### Inspection requested via web by Andrea Creek corrections made, t/s o/h n ok
|
Temporary Service | 2/24/2016 | 2/24/2016 | 2/24/2016 | P | FAIL |
Bob Reichert
|
|
|
TEMP POWER POLE INSPECTION Phone #: ###-#### Inspection requested via web by Andrea Creek called, left correction notice, NEC250.119 ground conductor shall not be black, 110.12(B) there shall not be broken parts such as 125v receptacle, screw missing from hub, 406.9(A)(B) 125 v receptacle shall be listed wr, 240 shall not feed 30 A receptacle with 50 A breaker
|