Final | 7/1/2016 | 7/1/2016 | 7/1/2016 | P | PASS |
James Ady
|
|
|
Phone #: ###-#### Inspection requested via web by Scott Campbell Correction made Final ok
|
Final | 6/30/2016 | 7/1/2016 | 7/1/2016 | A | FAIL |
James Ady
|
|
|
Contact is Ryan Wiedrich ###-#### Phone #: ###-#### Inspection requested via web by Scott Campbell Dead receps east base board
|
Electrical Rough-In | 6/3/2016 | 6/6/2016 | 6/6/2016 | A | PASS |
Rock A. Hudson
|
|
|
Ceiling inspection. Contact is Tony Hansen. Phone #: ###-#### Inspection requested via web by Scott Campbell Grid rough in ok cover
|
Electrical Rough-In | 6/1/2016 | 6/2/2016 | 6/2/2016 | A | FAIL |
Daryl DeGrange
|
|
|
Contact is Tony Hansen Phone #: ###-#### Inspection requested via web by Scott CampbellNEC 300.11(A) Secured in Place. Raceways, cable assemblies, boxes, cabinets, and fittings shall be securely fastened in place. Support wires that do not provide secure support shall not be permitted as the sole support. Support wires and associated fittings that provide secure support and that are installed in addition to the ceiling grid support wires shall be permitted as the sole support. Where independent support wires are used, they shall be secured at both ends. Cables and raceways shall not be supported by ceiling grids.
|
Electrical Rough-In | 5/18/2016 | 5/19/2016 | 5/19/2016 | P | PASS |
Daryl DeGrange
|
|
|
Contact is Ben MacDonagh Phone #: ###-#### Inspection requested via web by Scott Campbell rough-in ok cover consultation room walls
|
Electrical Rough-In | 3/25/2016 | 3/28/2016 | 3/28/2016 | P | PASS |
Rock A. Hudson
|
|
|
Contact is Tony Hansen Phone #: ###-#### Inspection requested via web by Scott Campbell East columns and 1/2 wall rough in ok cover
|